Seitenansicht 33
ZENNiO AVANCE Y TECNOLOGÍA _vwww.zennio.com
34
34
climate system can provide feedback of its on/off state by updating the object "[Climate x]
On/Off Indicator", and the indicator will be updated to reflect the new state of this object.
Box 2 (Temperature): This control allows the temperature setpoint to be configured
by the user. This setpoint value can be established in 3 different ways:
Absolute temperature: The 2-bytes object "[Climate x] Temperature Control" is
enabled, in order to send the desired setpoint to the climate system. Long or short
presses of the left (decrease) and right (increase) buttons allow the desired setpoint
to be established. A short press will increment or decrement the current value by
0.5ºC, and a long press by 1ºC. Upper and lower limits must be specified (ºC) in
order that the temperature range of the control may be bounded. Additionally the
object "[Climate x] Temperature Indicator" may be used to set the setpoint value
externally, for example to synchronize the setpoint amongst many Z41s in the same
climate zone.
Relative temperature (1-bit object): The 1-bit object "[Climate x] Temperature
Offset Control" is enabled. A short press of the right or left button will increment or
decrement, respectively, the current setpoint, by the value specified in the parameter
“Offset” in tenths of a degree. After each press, the setpoint value will be updated by
the offset and the new value will be displayed in the centre of the box, while the
value “0” (decrement) or “1” (increment) will be sent to the bus. Additionally the
object "[Climate x] Temperature Indicator" may be used to set the setpoint value
externally.
Relative temperature (float object): The 2-bytes object "[Climate x]
Temperature Control" is enabled, in order to increment/decrement (depending on the
button pressed: left/right) the value of the current setpoint in 0.5ºC, respectively. Only
short pressings are available. After every pressing, the setpoint value will be updated
with the new offset and will be shown in the centre of the box, and the value of the
offset applied with every pressing will be sent to the bus. It is possible to configure by
parameter the minimum and maximum offset that can be applied to the setpoint
(values between -15ºC and 15ºC). Additionally the object "[Climate x] Temperature
Indicator" may be used to set the setpoint value externally.
Box 3 (Mode): Allows selection of the operational mode of the climate system.
There are two options:
Seitenansicht 33