Section
Number
Name
Description
Size
Flags
THERMOSTAT 1
204
[T1] Offset Reset
Reset offset
1 bit
W
[T1] Setpoint Reset
Reset setpoint to default
1 bit
W
205
[T1] Mode
0=Cool; 1=Heat
1 bit
W
206
[T1] Mode Status
0=Cool; 1=Heat
1 bit
RT
207
[T1] On/Off
0=Off; 1=On
1 bit
W
208
[T1] On/Off Status
0=Off; 1=On
1 bit
RT
209
[T1] Control Variable (Cool)
2-point control
1 bit
RT
[T1] Control Variable (Cool)
PI control (PWM)
1 bit
RT
210
[T1] Control Variable (Heat)
2-point control
1 bit
RT
[T1] Control Variable (Heat)
PI control (PWM)
1 bit
RT
211
[T1] Control Variable (Cool)
PI control (Continuous)
1 byte
RT
212
[T1] Control Variable (Heat)
PI control (Continuous)
1 byte
RT
213
[T1] Additional Cool
Temp >= (Setpoint+Band) => “1”
1 bit
RT
214
[T1] Additional Heat
Temp <= (Setpoint-Band) => “1
1 bit
RT
THERMOSTAT 2
215
[T2] Temperature Source 1
External sensor measure
2 byte
W
216
[T2] Temperature Source 2
External sensor measure
2 byte
W
217
[T2] Special Mode
1-byte HVAC mode
1 byte
W
218
[T2] Special Mode: Comfort
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
219
[T1] Special Mode: Standby
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
220
[T1] Special Mode: Economy
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
221
[T1] Special Mode: Protection
0=Nothing; 1=Trigger
1 bit
W
0=Off; 1=On
222
[T1] Window Status (input)
0=Closed; 1=Open
1 bit
W
223
[T1] Comfort Prolongation
0=Nothing; 1=Timed Comfort
1 bit
W
224
[T1] Special Mode Status
1-byte HVAC mode
1 byte
RT